SB® Smart - up to 230 Amps

  • Selective Keyed Housings
  • Power and Auxiliary Contacts
  • 16 Last-Mate First-Break Auxiliary Power / Signal Poles
  • Sequencing of Auxiliary Contacts
  • Wire and Busbar Connections
  • Low Resistance Connection
  • Hot Plug Capable Contacts

Literature

Specifications

Literature Request Form

 

ELECTRICAL    
Current Rating (Amperes) 1    
Primary Contacts 230  
Auxiliary Contacts 15  
     
Operating Temperature 2 °C  °F
PC Housing -20° to 105° -4° to 221°
     
Voltage Rating (AC/DC) 600  
     
Dielectric Withstanding Voltage (AC) 2,200  
     
MECHANICAL    
Contact Wire Range Primary Power Auxiliary Power
   (AWG) 10 to 1/0 #24 to #12
   (mm²)  5.3 to 53.5 0.25 to 3.3
     
MAX Wire Insulation Diameter    
   (in) 0.65 0.12
   (mm) 16.25 3.2
     
AVG Contact Resistance (milli-ohms) 3 0.136 3.00
     
AVG Contact Retention Force    
   (lbf) 60 18
   (N) 267 80
     
Mating Cycles (no load) 10,000 10,000
     
Mating Cycles (hot plug @ 120V) 250 @ 50A 250@ 5A
     
Connector AVG Connect / Disconnect    
   (lbf) 82  
   (N) 365  
     
MATERIALS    
Standard Housing PC  
     
Flammability Rating UL94 V-0  
     
Wire Power Contact Copper alloy, silver plate  
     
PCB Power Contact Copper alloy, tin plate  
     
Auxiliary Pin Copper alloy, Au over Ni  
     
Auxiliary Socket BeCu, Au over Ni  
     
Auxiliary Socket Body Copper alloy, Sn Bright over NI  


1 - Based on: 105°C rated or better cable of the largest size.   Properly calibrated APP® 
      recommended tooling, and a 25°C ambient temperature.
2 - Limited by the thermal properties of the connector plastic housing.
3 - Use APP® recommended tooling only. Alternate tools may adversely affect the 
      performance of our connectors.
 

Drawings